N6400 over heating post power failure and/or Profile end
Refer to the N6400 concise product manual. 
 Page 2 - CONFIGURATION MODE Section 
 Parameter "rEc" can be set to "coLd (restart from controller setpoint after power-off), or "hot" (continues with profile after power-off if one was running). 
 Chose which you prefer. 
 Page 1 - BASE MODE Section 
 Check that the setpoint "SP" is set to a suitable safe value. 
 Page 1 - PROGRAM DEFINE MODE Section 
 After a program successfully completes, the final setpoint value of the last segment becomes the new controller setpoint value 
 Check that all programs end with a suitable safe final setpoint value, even ones you don't use, just in case you run it by mistake.