Blue Control will not communicate with ProVU, Pro96 or EC44 via the Configurator Lead
The Blue Control communication settings change depending on what is fitted into option slot A of the instrument. 
 The speed selected in Blue Control when uploading or downloading must be: 
 Slot A Empty = 19200 
 Slot A Fitted with Digital Input = 19200 
 Slot A Fitted with Ethernet Comms = 9600 
 Slot A Fitted with Auxiliary (RSP) Input = 4800 
 For all of the above options: Start and Stop bits must be 1, and Data bits 8. Parity must be None and address 1 
 Slot A Fitted with RS485 Comms = All settings must match the RS485 comms set in the Comm Settings in Configuration Mode. 
 This information is shown in the “Configuring The Connection” in the manual.







